Catch a fire while it is still a smell
The problem
A rack fan fails, a capacitor overheats, and the first alarm is a smoke detector in the corridor after the room is already lost.
Sensing
The logic
- Sample smoke every second; require 3 consecutive frames over 3 %/m, not one spike.
- Compare the thermal array against the inlet/outlet delta: a hot pixel 15 °C above its neighbours is a rack-local fault.
- Watch the VOC trend over 10 minutes; a slow rise with a flat smoke reading is the precursor window.
- If smoke is confirmed OR (hot pixel AND VOC rising), latch a local alarm and cut non-essential rack power via a contactor.
What the system does
Local strobe and buzzer, contactor drops non-critical circuits, a dry contact releases the fire panel, and a message goes out with the rack and the pixel.
What you get
The event is caught in the precursor window, the response is local and immediate, and the log shows which rack and which sensor spoke first.