Climate, light and irrigation that follow the plant instead of a schedule.

Vapour-pressure-deficit dosingLight-integral schedulingFlow-proven irrigationFrost and heat protection

The plant is the schedule

A timer waters the same amount in the rain and in a heatwave. A controller that reads the room can do better: it measures the water actually available to the roots, the light the canopy received, and the vapour-pressure deficit that drives transpiration — then doses to the demand.

The same controller holds the climate: it opens vents before the room overheats, runs the fan when humidity climbs, and protects the crop from frost with a staged heat ramp rather than a single on/off switch.

Four loops, one controller

  • Irrigation. Volumetric water content per zone, dosed in litres and proven by flow.
  • Climate. Temperature and humidity combined into VPD, with vent, fan and heat stages.
  • Light. Daily light integral from the lux sensor, with supplemental light only when the target is short.
  • CO₂. Enrichment only while the vents are closed and the room is occupied by plants, not by people.

Each loop has a manual override on the panel, a visible state and a log. Automation that cannot be overridden is a trap.

ZONE STATUS Auto
Bed A · tomatoes
VWC 38 % · TODAY 12.4 L
ok
Bed B · greens
VWC 44 % · TODAY 8.1 L
ok
Bed C · herbs
VWC 29 % · TODAY 0.0 L
warn
Tank
VWC 72 % · TODAY —
ok
FROST GUARD
Outside 4.1 °C · heat stage 1 armed
Protection

The failures that kill a crop.

Each one has a sensor and a rule that acts before the damage is visible.

Pump dry run

Float switch low plus no flow within 8 seconds: stop the pump and latch. The seal survives, and the log says which condition stopped it.

Broken line

Commanded zone with zero flow, or flow far above the learned band: close that zone valve and alarm. The other zones keep watering.

Frost

Outside temperature approaching the crop limit: stage heat, close vents, and send an alert with the trend, not a single number.

Heat spike

Canopy temperature above the limit with vents already open: start the fan, shade if fitted, and alarm. Never wait for the air sensor alone.

Sensor failure

An out-of-range or frozen reading is treated as a fault, not as data. The loop falls back to a safe schedule and says so.

Power cut

Valves fail closed, the controller keeps time on a battery-backed clock, and the schedule resumes with a catch-up dose, not a double dose.

Sensing

What this build listens to.

Full atlas

Capacitive soil moisture

Volumetric water content per zone, calibrated in the actual medium. 0.1 % resolution, ±3 % after calibration.

Temperature & humidity

Canopy and root-zone temperature with capacitive humidity, combined into vapour-pressure deficit.

Ambient light

Daily light integral from a lux sensor behind a diffuser, used to scale irrigation and supplemental light.

Turbine flow

Litres per zone, with a no-flow timeout that protects the pump and finds a broken line.

Float switch

Tank low and tank overflow as two independent signals, never one.

Rain gauge & wind

Suspend irrigation after real rain; close vents or retract shading before wind damage.

Your build

This pattern is reusable.

The same controller, rules and record serve a grow room, a machine, a pump station or a cold room. The sensors and the action change.