Arduino · sensors · automation

A room that watches itself,
and acts before you notice.

Custom systems built from sensing principles, not dashboards: smoke before fire, water before the rack, a door that reports itself, a panel that feels like equipment. Dozens of sensor families, real logic, physical action.

80 sensing principles · 25 server-room hazards · no cloud required
80Sensing principles catalogued with range, resolution, accuracy and interface
12Sensor families, from temperature to ionising radiation
25Server-room hazards with a detection rule and a local action
4Flagship builds, each specified down to the wiring and the logic
Server room sentinel

The room has twenty-five ways to fail. It should know all of them.

Smoke, water, humidity, explosive gas — and the rest: condensation, battery off-gassing, CO, refrigerant, ozone, oxygen depletion, filter loss, power events, forced doors, fan wear and suppression discharge. Each hazard gets a sensor, a confirmation rule and an action that happens locally.

  • Confirmed, not alarmed. Two independent signals or a sustained trend, so a speck of dust does not drop the room.
  • Local first. The contactor, valve and horn act on the controller; the message is a report, not the mechanism.
  • Named in the record. The zone, the rack, the pixel and the first sensor to speak.
ROOM SCHEMATIC Armed
LEAK ROPE · 4 ZONES
DIFF PRESS 132 Pa
CEILING: H₂ · SMOKE
SMOKE
0.4 %/m
WATER
Dry
GAS
2 % LEL
Job sheets

A problem, the logic, and the action it earns.

All 12 job sheets
01

Catch a fire while it is still a smell

Server room

The problem

A rack fan fails, a capacitor overheats, and the first alarm is a smoke detector in the corridor after the room is already lost.

The logic

  1. Sample smoke every second; require 3 consecutive frames over 3 %/m, not one spike.
  2. Compare the thermal array against the inlet/outlet delta: a hot pixel 15 °C above its neighbours is a rack-local fault.
  3. Watch the VOC trend over 10 minutes; a slow rise with a flat smoke reading is the precursor window.
  4. If smoke is confirmed OR (hot pixel AND VOC rising), latch a local alarm and cut non-essential rack power via a contactor.

What the room does

Local strobe and buzzer, contactor drops non-critical circuits, a dry contact releases the fire panel, and a message goes out with the rack and the pixel.

02

Find water before it finds the servers

Server room

The problem

Condensate from a CRAC unit pools under a raised floor and reaches a PDU before anyone walks in.

The logic

  1. Zone the leak rope: each 5 m section is its own digital input, so the alarm names the section.
  2. Treat a flood probe as the confirmation; a wet rope plus a dry probe is a spill, not a flood.
  3. Track dew point against the chilled-water pipe temperature; condensation risk is a computed number, not a guess.
  4. On a wet zone, stop the condensate pump, close the chilled-water valve and start the extract fan.

What the room does

Valve closes, pump stops, local alarm sounds, and the message names the zone and the time the rope first got wet.

03

Hold the room at temperature when a fan dies

Server room

The problem

One CRAC fan fails on a Friday night; the room climbs 1 °C every eight minutes and nobody knows until Monday.

The logic

  1. Read six temperature nodes: inlet, outlet, cold aisle top and bottom, hot aisle, and outside the door.
  2. Derive the room gradient; more than 5 °C top-to-bottom means airflow, not cooling capacity.
  3. Prove each fan is turning with a current clamp: a commanded fan with no current is a failed fan.
  4. Above 28 °C inlet, ramp the standby fan, open the economiser damper and page; above 32 °C, start a controlled shutdown of non-critical hosts.

What the room does

Standby fan ramps, damper opens, alert escalates, and the shutdown order is staged rather than panicked.

04

Detect the gas before it is an explosion

Server room

The problem

A battery string starts to off-gas, or a generator test pushes exhaust into the intake, and the room has no nose.

The logic

  1. Catalytic sensor watches 0–100 % LEL; alarm at 10 % LEL, trip at 20 % LEL.
  2. Hydrogen at the ceiling confirms battery off-gassing; CO at the intake confirms exhaust ingress.
  3. Oxygen below 19.5 % means displacement, not combustion; treat it as a different emergency.
  4. Above 10 % LEL: force ventilation, inhibit battery charging, drop non-essential power and alarm locally.

What the room does

Ventilation runs at full speed, the charger is inhibited, a dry contact signals the fire panel, and everyone gets a message that names the gas.

05

Prove the walk-in stayed cold

Cold chain

The problem

A door is left ajar, the compressor is running but not cooling, and the first evidence is spoiled stock.

The logic

  1. Two temperature probes: air and product-simulant, because air recovers fast and product does not.
  2. Door contact starts a timer; more than 3 minutes open is a door alarm, not a temperature alarm.
  3. Compressor current proves it is running; a running compressor with a rising temperature is a refrigerant fault.
  4. Log every 60 s with a rolling 30-day record; alarm at 4 °C for 10 minutes or 8 °C for 2 minutes.

What the room does

Alarm at the door and at the phone, with the graph attached; the log is exportable for the audit.

06

Interlock the tools to the extraction

Workshop

The problem

The extractor fills up, airflow drops, and people keep cutting because nothing tells them the air is getting worse.

The logic

  1. Differential pressure across the filter gives loading; below 80 Pa of draft, the filter is blocked.
  2. Particulate above 150 µg/m³ for 2 minutes with the extractor commanded on means capture has failed.
  3. Current clamp proves the extractor is actually running, not just switched on.
  4. Interlock: remove the run-enable from the tool relay and sound a local horn until airflow is restored.

What the room does

The tool relay drops, the horn sounds, and the dashboard shows filter loading rather than a vague 'air quality' score.

Control panels

An interface you can operate with a gloved hand.

Momentary buttons, maintained switches, selector and key switches, mushroom E-stops, toggles, rotary encoders, faders, joysticks, levers and foot pedals — wired to character LCDs, OLED, colour TFT, seven-segment displays, bar graphs and status beacons.

The E-stop interrupts the contactor coil directly. Software observes, logs and reports; it never grants permission to a safety chain.

Panel · demo
PLANT ROOM 01AUTO
22.6 °C
SETPOINT 23.0 · PUMP 1 RUN
FLOW12.4 L/M
DOORSEALED
MODE AUTOSAFETY OKLINK OK
Full interactive panel on the build page →
Engineering standard

The parts that make it survive a Tuesday.

The sensor is the easy part. These are the decisions that separate a demo from equipment.

Fail safe by wiring

Safety functions interrupt power directly: normally-closed contacts, a latching E-stop, a contactor coil in series. Software can only observe and report.

Debounce, filter, hysteresis

A 20 ms button rule, a median-of-five ADC filter and a 2 °C dead band. Without them a stable room looks like a fireworks display.

Read back every output

An auxiliary contact proves the contactor closed. A command is an intention; feedback is a fact. Alarm on the difference.

Calibrate against a reference

Gas cells get span gas, pH gets buffers, load cells get known masses, temperature gets an ice point. An uncalibrated alarm is decoration.

Isolate and protect

Optocouplers on every external input, TVS and fusing on long runs, separate mains and low-voltage glands, and a star ground. Most 'sensor faults' are electrical.

Log locally, report honestly

Ring buffer on the controller, SD card or flash for a month, and a report that states the gap when the link was down. Never a green badge with nothing behind it.

Start a brief

Tell me the room, the machine or the panel that keeps failing.

Bring the condition you need to detect, the action that must follow, and the environment it lives in. I will come back with the sensing principle, the logic and the build.

  • Server room, plant room, cold room, greenhouse or workshop
  • Control panel, test rig or operator console
  • Machine monitoring, leak detection, access or power
  • One controller, local logic, a record you can read

Stored locally, then delivered to the central Kituwa intake. No marketing list.