Catch a fire while it is still a smell
The problem
A rack fan fails, a capacitor overheats, and the first alarm is a smoke detector in the corridor after the room is already lost.
The logic
- Sample smoke every second; require 3 consecutive frames over 3 %/m, not one spike.
- Compare the thermal array against the inlet/outlet delta: a hot pixel 15 °C above its neighbours is a rack-local fault.
- Watch the VOC trend over 10 minutes; a slow rise with a flat smoke reading is the precursor window.
- If smoke is confirmed OR (hot pixel AND VOC rising), latch a local alarm and cut non-essential rack power via a contactor.
What the room does
Local strobe and buzzer, contactor drops non-critical circuits, a dry contact releases the fire panel, and a message goes out with the rack and the pixel.