Vibration, current and temperature fused into a wear trend you can act on before the line stops.

Bearing-band energy trendPer-speed baselinesCurrent and thermal cross-checksStaged trip, never a surprise

Wear has a sound

A bearing that is failing changes the vibration spectrum weeks before it seizes. The energy moves into a narrow band at the bearing's defect frequency and its harmonics. A single RMS number hides that; a band-energy trend against a learned baseline exposes it.

The controller samples the accelerometer at 1–3 kHz for a short window every minute, computes RMS and the band energy, and stores the trend. Current and winding temperature rule out an electrical cause. Speed from a hall sensor keeps the baseline honest across the machine's operating range.

What it catches — and what it does not

  • Catches: bearing degradation, imbalance, looseness, belt wear, cavitation, a developing misalignment.
  • Catches: an electrical fault through current and thermal cross-checks.
  • Does not catch: a sudden fracture with no precursor. No trend system does; that is what inspection and protection relays are for.
  • Does not replace: a certified machine-protection system. It informs maintenance; it does not guard a person.
BEARING BAND · 14 DAYS +4.8 dB
RMS
2.14 mm/s
CURRENT
14.2 A
WINDING
68 °C
The trip ladder

A warning you can plan around, then a stop you can trust.

The threshold is per speed and per machine, learned from the machine itself. A vendor's generic limit is a starting point, not a baseline.

Learn

One week of running at each speed builds the baseline: RMS, band energy, current and thermal. The machine teaches the controller what normal is.

Watch

Every minute is compared against the baseline for the current speed. A 6 dB rise in the bearing band for three hours opens a maintenance ticket.

Trip

At 12 dB, or on a shock event above the learned limit, the controller drops the run-enable. The trip is staged and announced, never a surprise.

Cross-check

A rising current at constant load is mechanical. A rising temperature at constant current is electrical. The pair tells you which trade to call.

Prove the fix

After the repair, the same baseline proves the bearing actually improved. A repair without a before-and-after trend is a story.

Keep it honest

The controller reports its own gaps: a missed sample, a saturated accelerometer, a speed it has never seen. A trend with hidden holes is worse than no trend.

Sensing

What this build listens to.

Full atlas

3-axis accelerometer

Vibration sampled at 1–3 kHz, with RMS and bearing-band energy computed on the controller.

Current transformer

Motor current to separate a mechanical fault from an electrical one, and to prove the motor is actually running.

Platinum RTD

Winding or bearing temperature with a stable, calibratable reading, not a thermistor guess.

Hall sensor

Shaft speed and position, so every baseline is indexed to the speed the machine was actually running.

Piezo shock sensor

Impact and knock events that a slow RMS trend would smooth away.

Contactor feedback

Proof that the run-enable actually opened when the controller asked it to.

Your build

This pattern is reusable.

The same controller, rules and record serve a grow room, a machine, a pump station or a cold room. The sensors and the action change.